B1 FIRE RESISTANT FOAM
- Stock: In Stock
- Brand: RAWLPLUG
- Model: RAW R-RPP-B1
- Weight: 0.90kg
- Dimensions: 78.00cm x 76.00cm x 352.00cm
- SKU: RAW R-RPP-B1
- UPC: 5906675285047
Products Sold: 0
Product Views: 23
R 473.80
Ex Tax: R 412.00
R-RPP-B1 Fire Resistant Foam
B1 - Low-pressure, one-component polyurethane fire-resistant foam with applicator gun.
- Fire-resistant - EI 120 fire resistance, providing technical approval criteria are fulfilled
- Insulates against smoke and gas
- Self-extinguishing.
- Ideal for mounting, sealing and soundproofing.
- Excellent sound and thermal insulation properties.
- Extremely rapid curing – workable 40 minutes after optimum application.
- Resistant to mould and fungi.
Installation guide
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
- Wear protective gloves. Ensure surfaces are free from dust, dirt or debris.
- Before using, make sure that the can temperature is above zero (optimum +20°C). Application temperature from +5°C up to +30°C.
- Shake can vigorously for 30 seconds to mix properly components.
- Screw gun onto the can. Hold can upside-down during application.
- Moisten surfaces with water prior to application.
- Fill gaps from down to up, zigzag motion, alternating from one wall to the other. Fill gaps to approximately 60 % volume. Max. wide of the gap 3-4 cm. Wider gaps should be applied after hardening of the previous layer. Each layer should be moistened with water using a spray.
- Once fully hardened, foam must be protected from UV exposure by coating with plaster, paint, acrylic or silicone.
- In the event of a stoppage exceeding five minutes duration, wipe the nozzle with cleaner for foam applicator.
- After removing the applicator gun from the can, wipe down the nozzle and gun (internal and external surfaces) using a cleaner.
Features:
- Fire-resistant - EI 120 fire resistance, providing technical approval criteria are fulfilled
- Insulates against smoke and gas
- Self-extinguishing.
- Ideal for mounting, sealing and soundproofing.
- Excellent sound and thermal insulation properties.
- Extremely rapid curing – workable 40 minutes after optimum application.
- Resistant to mould and fungi.
Applications
- For all applications with a legal requirement for fire resistance class B-1 according to DIN 4102
- For fireproof installation and assembly of PVC, wood & aluminum frames.
- For fire-resistant sealing of joints in roofing, walls & ceilings.
- For fire-resistant insulation of conduits and fittings.
- Filling frame structures
Base materials
Approved use in:
- Wood
- Timber
- Structural Steel
- Stainless steel
- Plastic
- Concrete
- Metal Sheet & Profiles
Technical Data
Parameter | Value | Methods | |
Application temperature | [°C] | +5 ÷ +30 | |
Can temperature | [°C] | +20 | |
Efficiency | [dm3] | max. 45 | |
Colour | - | red | |
Skin formation time | [min] | 12-16 | 20°C, RH 90% |
Pretreatment time | [min] | 30-40 | 20°C, RH 90% |
Complete hardening time | [h] | 24 | |
Fire resistance class | - | B-s1, dO | PN-EN 13501-1+A1:2010 |
Density(kg/dm3) | [%] | 25 ± 10 | PN-EN ISO 845:2000 |
Dimensional stability | [%] | +/- 2 | 40°C, RH 95%, 24 hrs |
Water absorption after 24h | [kg/m3] | 0,5 | PN-EN 1609:1999 |
Tensile strength | [kPa] | ≥ 50 | PN-EN 1607:1999 |
Compressive strength | [kPa] | ≥ 100 | PN-EN 826:1998 |
Thermal resistance (upon hardening) | [°C] | -50 ÷ +90 | |
Thermal conductivity | [W/mK] | 0.034 | |
Preparations solublity | - | Acetone, before hardening | Cleaner RPC-0500 |
Soundproofing coefficient | [dB] | 61 | EN 12354-3 |
Volume | [ml] | 750 | |
VOC Content | [g/l] | 169 | calculated |
Fire resistance classification | - | EI 120 | EN 1366-4 |
Unlimited Blocks, Tabs or Accordions with any HTML content can be assigned to any individual product or to certain groups of products, like entire categories, brands, products with specific options, attributes, price range, etc. You can indicate any criteria via the advanced product assignment mechanism and only those products matching your criteria will display the modules.